Single-Phase Power Calculator
For household and small business supplies (for example 230 V or 120 V). Enter the voltage, current and power factor to get real power (kW), apparent power (kVA) and reactive power (kvar), or start from a kW or kVA rating to find the current.
0 to 1, or a percentage. From the nameplate or a meter.
Formula: S = V × I, P = S × PF, Q = S × sin φ.
These are textbook formulas for learning, checking and planning. They do not size cables, fuses, breakers or earthing, and they are not a substitute for a licensed electrician. Any wiring work must follow your local electrical code.
Single-phase AC power
Most homes, shops and small offices have a single-phase supply: one live wire and a neutral, at 230 V or 240 V in much of the world and 120 V in North America. On AC, voltage and current both swing back and forth, and with many loads they do not peak at the same moment. That is why three kinds of power appear.
Watts, volt-amperes and var
Real power (W or kW) is the part that does useful work and is what most household meters bill. Apparent power (VA or kVA) is simply volts times amps; cables, fuses, inverters and generators have to carry it. Reactive power (var or kvar) is the part that flows back and forth each cycle without doing work.
They form a right-angled triangle. Real power is the base, reactive power the height and apparent power the long side. The power factor is real ÷ apparent, the cosine of the angle between them.
Two directions
Choose volts and amps when you have readings from a meter. For 230 V, 6.5 A and a power factor of 0.92, the page gives about 1.38 kW, 1.5 kVA and 0.59 kvar.
Choose kW or kVA when you know a rating and want the current. A 3 kW load at 230 V and 0.9 draws about 14.5 A.
Backup power example
Inverters and UPS units are rated in both kVA and kW. A 1 kVA unit rated 800 W can supply 800 W only if the load’s power factor is at least 0.8. A computer power supply with a power factor near 1 hits the watt limit first, while a pump motor with 0.7 hits the kVA limit first. Working out both figures here avoids a unit that trips under load.
Good habits
Use the nameplate current where possible, because it already includes the motor’s efficiency. Remember that motors draw several times their running current while starting. For three-phase equipment, switch to the three-phase power calculator, and to improve a poor power factor see the power factor calculator.
How to use Single-Phase Power Calculator
- Choose what you know: volts and amps, kW, or kVA.
- Type the voltage, the current or power, and the power factor.
- Read the results and the working, which shows each formula with your numbers.
Privacy: how it works
Calculations run in your browser. The values you enter are not sent anywhere.
Frequently asked questions
How do I calculate single-phase power?
Apparent power is volts × amps (VA). Real power is that times the power factor. 230 V × 10 A = 2.3 kVA, and with a power factor of 0.8 the real power is 1.84 kW.
Where do I find the power factor?
On the nameplate or data sheet (shown as cos φ or PF), or from a power meter. Heaters, kettles and filament lamps are 1. Motors and older fluorescent fittings are often 0.6 to 0.9.
Is a 5 kVA inverter enough for a 5 kW load?
Only if the load's power factor is 1. A 5 kW load at 0.8 needs 6.25 kVA. Inverters and UPS units often state both a kVA and a kW limit; the load must be within both.
Related tools
- Three-Phase Power Calculator
- Power Calculator (Watts)
- Power Factor Calculator
- Current Calculator (Watts to Amps)